GMF 730 NR IR

Product no.: GMF 730 NR IR (Gas type: further on request, Measuring range: further on request)

BUS wet areas sensor

Measuring range: 0 ... 100% LEL
Measuring principle: infrared absorbtion with reference channel
Lifetime > 5 years
Accuracy: <+- 1% of measuring range
Response time T90:       <30 sec
Ambient: -20..+50°C, 0..95% RH, 700 - 1300 hPa
Suitability: wet areas, sewage treatment plants
Housing: polyester, glass fiber reinforced, LxWxD: 110x90x60 mm
Protection class: housing: IP66, RAL 7000
Gas entry: diffusion
Output signal: digital, RS485
CE-conformity: emission: residential: immunity for industrial environments
Supply: 12..36V DC, 60 mA @ 24V DC
Connection cable: up to 1200 m: JY(St)Y 2x2x0,8 mm
   

Operating instruction

Selection: GMF 730 NR IR

Product no. Gas type Measuring range Price
GMF 730 NR IR CO2 5V Carbon dioxide 0...5 vol%
GMF 730 NR IR CO2 10V Carbon dioxide 0...10 vol%
GMF 730 NR IR HC UEG Hydrocarbon 0...100% LEL
GMF 730 NR IR CH4 UEG Methane 0...100% LEL
GMF 730 NR IR PRP UEG Propane 0...100% LEL
GMF 730 NR IR further on request further on request
Browse this category: Standard Digital-BUS