Series 230 H for combustible gases and vapours

Product no.: GMF 230 H (Gas type: further on request, Measuring range: further on request)

BUS-sensor with semiconductor sensor for combustible gases and solvents

Suitability: dusty, dirty areas
Gas type: combustible gases and solvents
Measuring range: 0...100 %LEL
Accuracy: <+-5% FS
Response time T90: < 20 sec
Temperature range: -20..+50°C (environment)
Humidity range: 0..95% r.F.
Pressure range: 700-1300 hPa
Housing: aluminium, LxWxH: 80x80x60mm
Protection type: IP65
Gas inlet: diffusion, sinter filter, IP44
BUS-Topology: RS 485
Lifetime: >10 years in dry, oil-free environment
CE-conformity: distribution: residential, immunity: industrial area
Weight: 430g
Supply: 12-36V DC
Current
consumption:
ca. 30 mA @ 24 V DC
Connecting cable: JY (ST) Y 2x2x0,8 mm²
   

Operation instruction

Selection: GMF 230 H for combustible gases and vapours

Product no. Gas type Measuring range Price
GMF 230 H ACT UEG Acetone 0...100 % LEL
GMF 230 H ACN UEG Acetylene 0...100 % LEL
GMF 230 H HC UEG Gasoline vapors 0...100 % LEL
GMF 230 H BUT UEG Butane 0...100 % LEL
GMF 230 H ETA UEG Ethane 0...100 % LEL
GMF 230 H ETL UEG Ethanol 0...100 % LEL
GMF 230 H ETB UEG Ethyl benzene 0...100 % LEL
GMF 230 H ETN UEG Ethylene 0...100 % LEL
GMF 230 H CH2O 2000 Formaldehyde 0...2000 ppm
GMF 230 H HEP UEG Heptane 0...100 % LEL
GMF 230 H HEX UEG Hexane 0...100 % LEL
GMF 230 H IPRPL UEG Isopropanol 0...100 % LEL
GMF 230 H CH4 UEG Methane 0...100 % LEL
GMF 230 H MTL UEG Methanol 0...100 % LEL
GMF 230 H MEK UEG Methyl ethyl ketone 0...100 % LEL
GMF 230 H NON UEG Nonane 0...100 % LEL
GMF 230 H PRP UEG Propane 0...100 % LEL
GMF 230 H STY UEG Styrene 0...100 % LEL
GMF 230 H THF UEG Tetrahydrofuran 0...100 % LEL
GMF 230 H TOL UEG Toluene 0...100 % LEL
GMF 230 H H2 UEG Hydrogen 0...100 % LEL
GMF 230 H further on request further on request
Browse this category: Standard Digital-BUS